High Mast Cable
EPR-insulated, rubber-sheathed flexible cable for the lantern carriage of high mast lighting systems. 1100 V grade, 5-core, manufactured to IS 9968.
BMI Cables manufactures high mast flexible cables that carry power from the base compartment of a high mast to the luminaires mounted on its lantern carriage. Because the carriage is lowered and raised for maintenance, the cable travels with it and must withstand repeated flexing, long suspended runs and continuous outdoor exposure for the life of the installation.
The standard construction uses tinned copper Class 5 conductors, heat-resisting EPR insulation, an overall cotton-yarn braid and a heavy-duty heat-, oil- and flame-retardant polychloroprene (HDOFR PCP) sheath. Standard sizes are 5-core 2.5, 4.0 and 6.0 mm². Where the project calls for it, the same cable is supplied in other core counts (3, 4, 7 and 8-core), with a stainless-steel wire braid in place of or over the cotton braid, or with a PVC or FRLS sheath — see variants and special requirements below.
How the Cable Is Used in a High Mast System
High mast lighting uses poles commonly 16 m to 30 m tall carrying several luminaires on a ring-shaped lantern carriage. A winch in the base compartment lowers the carriage to ground level on stainless-steel wire ropes that pass over a pulley at the head frame. The high mast cable is the flexible multicore cable that feeds the luminaires: it is terminated at the MCB or terminal block in the base compartment, runs up inside the mast, passes over the head frame and comes down to the junction box on the carriage.
Three features of this duty drive the cable design. Between the head frame and the carriage the cable hangs under its own weight for the full height of the mast, and it coils and uncoils in the base compartment as the carriage moves. It is exposed to sun, rain, dust and wide temperature swings for the mast’s design life of 25 years or more, normally without intermediate joints. And because masts are usually fed three-phase with the luminaires split across phases, a 5-core cable (three phases, neutral and earth) is the most common requirement in Indian tender specifications, typically 2.5 to 6 mm².
Construction
- Conductor — multi-stranded tinned annealed copper, Class 5 to IS 8130. Tinning protects the copper at terminations and in long-term contact with rubber compounds.
- Insulation — heat-resisting EPR, Type IE-2 to IS 6380. Maximum continuous conductor temperature 90 °C, 250 °C under short circuit. Core colours red, yellow, blue, black and green.
- Lay-up and braid — cores laid up with a right-hand lay; an overall cotton-yarn braid binds the assembly and provides a stable base for the sheath under flexing.
- Sheath — heavy-duty HOFR PCP (polychloroprene), Type SE-4 to IS 6380, black. Resistant to weathering, ozone, oil and abrasion. Printed every metre with make, size, voltage grade and year.
Technical specifications
Typical values for BMI’s standard 5-core high mast flexible cable, 1100 V grade. Dimensions and weights are approximate; the approved datasheet for a specific order governs.
| Parameter | 5C × 2.5 mm² | 5C × 4.0 mm² | 5C × 6.0 mm² |
|---|---|---|---|
| Conductor diameter (approx.) | 2.2 mm | 2.8 mm | 3.3 mm |
| EPR insulation, nominal thickness | 1.0 mm | 1.0 mm | 1.0 mm |
| Diameter over laid-up cores (approx.) | 12.0 mm | 14.0 mm | 15.0 mm |
| HD HOFR PCP sheath, nominal thickness | 1.5 mm | 2.5 mm | 2.5 mm |
| Overall diameter (approx.) | 16.0 mm | 20.0 mm | 22 mm |
| Weight (approx.) | 350 kg/km | 505 kg/km | 595 kg/km |
| Max. DC conductor resistance at 20 °C | 8.21 Ω/km | 5.09 Ω/km | 3.39 Ω/km |
| Current rating (90 °C conductor, 30 °C ambient) | 20 A | 31 A | 44 A |
| Minimum bending radius | 6 × overall diameter | ||
| Safe pulling force | 9 × D² newtons (D = overall diameter in mm) | ||
| Common to all sizes | Value |
|---|---|
| Voltage grade | 1100 V, to IS 9968 (Part 1) |
| Max. conductor temperature | 90 °C continuous; 250 °C short circuit |
| High-voltage test | 3 kV rms for 5 minutes, core to core |
| Insulation resistance constant | 3670 MΩ·km minimum at 27 °C; 3.67 MΩ·km at 90 °C |
| Insulation / sheath tensile strength (min.) | 4.2 N/mm² / 11.0 N/mm² |
| Insulation / sheath elongation at break (min.) | 200 % / 250 % |
Values above are for the standard cotton-braided 5-core construction. Dimensions and weights of 7-core, 8-core and stainless-steel braided variants differ; a datasheet for the exact construction is issued against the enquiry.
Variants and special requirements
High mast tenders and OEM drawings do not always call for the standard 5-core cotton-braided cable. The constructions below are regularly specified and are manufactured by BMI on the same EPR / HOFR PCP base.
Core counts: 3, 4, 5, 7 and 8-core
5-core (three phases, neutral and earth) covers a single three-phase circuit and is the most common requirement. Other core counts are used when the carriage wiring is different:
- 3-core and 4-core — Single-phase masts, or three-phase masts where the earth is taken through the mast body and carriage rather than a cable core.
- 7-core and 8-core — Masts with two separately switched circuits on the carriage (for example half-night switching, where part of the luminaires are turned off after midnight), or where the carriage also carries an aviation obstruction lamp, photocell or timer control, CCTV or a dimming/communication line that needs its own cores. 8-core gives two phase-plus-neutral groups with earth, or one three-phase circuit plus spare and control cores.
All multicore variants use the same Class 5 tinned copper conductors and EPR insulation; core identification is by colour or by printed numbers as the specification requires.
Stainless-steel wire braiding
Some specifications call for a stainless-steel wire braid over the laid-up cores (under the sheath) or over the sheath. It is asked for on taller masts, coastal and industrial sites and in projects where the client wants the cable to carry its own suspended weight without loading the conductors. The braid does four things:
- Tensile support — A 30 m length of 5-core cable weighs 10–18 kg and hangs from the carriage termination and over the head-frame pulley. The steel braid takes this load along the cable’s length instead of the copper strands and insulation.
- Abrasion and crush protection — Where the cable rubs against the head-frame pulley, the inside of the mast and the door frame of the base compartment during every raise-and-lower cycle.
- Corrosion resistance — Stainless steel (rather than galvanised steel) is used because the cable is outdoors for decades, often at coastal or chemical-plant sites; it can also be bonded as a supplementary earth.
The braid does add weight and reduces flexibility, so it is normally specified only where the tender or the mast manufacturer requires it. BMI supplies either construction; state it clearly at enquiry.
Sheath and length options
HOFR PCP is standard. PVC insulation & sheathed EPR cable is accepted in some municipal tenders; FRLS or low-smoke sheaths are specified where the mast stands inside a building, tunnel or station. Cables are supplied as one continuous length per mast (for example 33.5 m coils for a 30 m mast) or in drum lengths for site cutting, with project-specific colour schemes and legend printing as required.
Why a rubber cable for high mast service
A high mast cable is selected for how it behaves over years of outdoor, suspended, intermittently flexed service, not only for its current rating.
Why not an ordinary flexible or trailing cable
A general-purpose flexible or trailing cable is designed to lie on a surface or to be reeled, not to hang vertically for 20–30 m while being bent over a pulley every time the carriage moves. In high mast service its own weight pulls continuously on the conductors at the carriage termination; combined with flexing at the head frame, the copper strands fatigue and break one by one, and a PVC sheath hardens and cracks in sunlight. The result is an intermittent fault or an open circuit on one phase, usually a few years into service. Replacing it is not a minor job: the carriage has to be lowered, the old cable withdrawn through the mast, a new length threaded up inside the mast and over the head frame, and the carriage re-terminated and re-raised — a day’s work for a trained crew with the mast out of service, often more than the cost of the cable itself. A purpose-made high mast cable with fine-stranded tinned conductors, EPR insulation, a binding braid and a weather-resistant HOFR PCP sheath (with stainless-steel braiding where specified) is built so that this replacement is not needed within the life of the mast.
Flexibility
Class 5 fine-stranded conductors and elastomeric insulation and sheath keep the cable supple through repeated bending over the head-frame pulley and coiling in the base compartment, in cold weather as well as hot.
Weather, ozone and UV resistance
The PCP sheath is formulated for continuous outdoor exposure. Unlike general-purpose PVC, it does not harden and crack with sunlight and temperature cycling over the mast’s service life.
Thermal headroom
EPR insulation rated at 90 °C gives margin for enclosed, sun-heated base compartments and for the conductor temperatures reached when the cable is coiled rather than hung in free air.
Oil resistance and flame retardance
HOFR grading of the sheath covers incidental oil from the winch gearbox in the base compartment and gives flame-retardant behaviour where the cable passes through the compartment and mast.
Selection guidance
Size for load and voltage drop
Add up the luminaire wattage on the carriage, allowing for control gear and future additions (LED fittings have reduced loads considerably). Check voltage drop over the full cable length — mast height plus the run inside the base compartment — not the mast height alone. For most LED installations on 16–30 m masts, 2.5 or 4 mm² is sufficient; 6 mm² is used for higher loads or longer runs.
Match the length to the winch and mast
The cable must reach from the terminals in the base compartment, over the head frame and down to the carriage junction box, with slack for the carriage at ground level. Order cut lengths per mast, or confirm the drum length the installer will cut from.
Count the circuits, not just the luminaires
One three-phase circuit needs 5 cores. If the carriage has two switched groups of luminaires, an obstruction lamp, or control wiring, specify 7 or 8 cores so that a second cable does not have to be hung alongside the first.
Choose the sheath and braid for the site
HOFR PCP is the standard for outdoor, UV-exposed and oil-adjacent service. EPR insulated, PVC sheathed cable is accepted in some tenders; FRLS or low-smoke sheaths may be required inside buildings or tunnels. Specify stainless-steel wire braiding where the tender, the mast manufacturer or the site (tall masts, coastal or chemical environments, rodent-prone compartments) calls for it. Confirm the specified type before ordering.
State the documentation required
Government and PSU tenders typically ask for a manufacturer’s test certificate, a type-test report to the applicable IS standard and sometimes third-party inspection. Stating these at enquiry stage ensures they are included in the quotation.
Standards and testing
BMI high mast cables are manufactured and tested to the Indian Standards applicable to elastomer-insulated flexible cables. The mast structure is governed by separate standards (for example IS 875 Part 3 for wind loading) that do not apply to the cable.
| Reference | Area covered |
|---|---|
| IS 9968 (Part 1) | Elastomer-insulated cables for working voltages up to and including 1100 V — construction, dimensions and tests |
| IS 8130 | Conductors for insulated electric cables and flexible cords — Class 5 flexible tinned copper |
| IS 6380 | Elastomeric insulation and sheath compounds — EPR Type IE-2 insulation, HOFR PCP Type SE-4 sheath |
Routine tests include conductor resistance, the high-voltage test (3 kV rms, 5 minutes, core to core) and insulation resistance. Type and acceptance tests — tensile strength and elongation of insulation and sheath, hot-set test on insulation, and conductor annealing — are carried out as per the standard and the agreed quality plan. A manufacturer’s test certificate accompanies every dispatch, and third-party inspection by RITES, Bureau Veritas, TUV or a client-nominated agency can be arranged.
FAQ - High Mast Cable
A flexible multicore copper cable, most commonly 5-core, runs from the base compartment to the lantern carriage. Indian tender specifications typically call for 5-core 2.5 to 6 mm² EPR-insulated copper cable, rubber or PVC sheathed, rated 1100 V. The underground feed from the feeder pillar to the mast base is a separate armoured cable.
A 5-core cable carries three phases, neutral and earth, so the luminaires on the carriage can be distributed across phases within a single circuit. Where a mast is fed single-phase or has more than one circuit, 3-core or other core counts are supplied to suit.
The cable hangs outdoors for the life of the mast and flexes every time the carriage is raised or lowered. EPR insulation stays flexible across a wide temperature range and is rated 90 °C, while a PCP sheath resists sunlight, ozone, oil and abrasion. General-purpose PVC tends to stiffen and crack under long UV exposure and repeated flexing.
Size depends on the connected luminaire load, the supply arrangement and the total cable length. For most LED installations on 16–30 m masts, 2.5 or 4 mm² is sufficient; 6 mm² is used for higher loads or longer runs. Share the mast height and luminaire schedule and BMI will confirm the size and voltage drop.
A manufacturer’s test certificate is issued with every dispatch. Type-test reports to IS 9968 and third-party inspection by agencies such as RITES, Bureau Veritas, TUV or a client-nominated agency can be arranged against the order.
Yes. A stainless-steel wire braid can be applied over the laid-up cores or over the sheath. It carries the suspended weight of the cable, protects against abrasion at the head-frame pulley and inside the mast, and resists rodents and corrosion at coastal or industrial sites. It is supplied where the tender or mast manufacturer specifies it; the standard construction uses a cotton-yarn braid.
BMI Cables is a leading wires and cables manufacturer in India, supplying high-performance electrical cables to industrial, infrastructure, and OEM sectors since 2003. ISO 9001:2015 certified.
Useful Links
Contact Us
Head Office
SF-1, 1st Floor, Bhikaji Cama Bhawan, Bhikaji Cama Place, New Delhi 110066, India
Works
F-81 to 84, & G-108, RIICO Industrial Area, Khushkhera, Bhiwadi, Distt. Alwar, Rajasthan- 301707
+91 92570 35793
sales1@bmicables.com
Copyright 2026, BMI Cables Pvt. Ltd. All Rights Reserved.